ATC Series
THREE-PHASE AUTOTRANSFORMERS
Reversible three phase auto transformer not C.C resistant.
Standard Features
Power: 0,5kVA – 50kVA
Voltages: 230V(220V)-400V(380V)
Network frequency: 50/60Hz
Thermal Class: F
Over Temperature: classe B
Ambient Temperature: max.50°C
Degree of Protection: IP20
Class of Insulation: I
Special Features (optional)
Power: 0,3kVA – 200kVA
Voltages: min.24V-max.1000V
Network frequency: 40-1000Hz
Thermal Class: A,B,E e H
Over Temperature: A,B,E,F e H
Ambient Temperature: >-20/<80°C
Degree of Protection: IP00-IP66
NB:
mechanical and / or electrical listed in the tables may be changed without notice
DOWNLOAD:
Download PDF version of this page |
POWER | V1 | V2 | CODE | MECHANICAL CHARACTERISTICS | ||||||
KVA | A (mm) | B (mm) | C (mm) | f (mm) | s (mm) | d (mm) | Weight(kg) | |||
0,5 | 230 | 400 | ATC000K5.001 | 150 | 75 | 140 | 100 | 60 | 6 | 3,3 |
1 | 230 | 400 | ATC001K0.001 | 150 | 85 | 140 | 100 | 70 | 6 | 5,4 |
1,5 | 230 | 400 | ATC001K5.001 | 180 | 95 | 165 | 145 | 77 | 6 | 8,2 |
2 | 230 | 400 | ATC002K0.001 | 180 | 105 | 165 | 145 | 86 | 6 | 9,2 |
2,5 | 230 | 400 | ATC002K5.001 | 180 | 115 | 165 | 145 | 97 | 6 | 10,3 |
3 | 230 | 400 | ATC003K0.001 | 180 | 130 | 165 | 145 | 110 | 6 | 13,8 |
4 | 230 | 400 | ATC004K0.001 | 240 | 110 | 220 | 200 | 90 | 10 | 16,2 |
5 | 230 | 400 | ATC005K0.001 | 240 | 120 | 220 | 200 | 100 | 10 | 18,4 |
7,5 | 230 | 400 | ATC007K5.001 | 240 | 130 | 220 | 200 | 110 | 10 | 20,7 |
10 | 230 | 400 | ATC010K0.001 | 300 | 110 | 280 | 250 | 95 | 10 | 31 |
12,5 | 230 | 400 | ATC012K5.001 | 300 | 120 | 280 | 250 | 105 | 10 | 35 |
15 | 230 | 400 | ATC015K0.001 | 300 | 130 | 280 | 250 | 115 | 10 | 40 |
20 | 230 | 400 | ATC020K0.001 | 300 | 140 | 320 | 250 | 125 | 10 | 46 |
25 | 230 | 400 | ATC025K0.001 | 360 | 150 | 370 | 300 | 125 | 10 | 53 |
30 | 230 | 400 | ATC030K0.001 | 360 | 170 | 370 | 300 | 145 | 10 | 66 |
40 | 230 | 400 | ATC040K0.001 | 420 | 195 | 420 | 350 | 130 | 12 | 98 |
50 | 230 | 400 | ATC050K0.001 | 420 | 210 | 420 | 350 | 150 | 12 | 104 |
POWER | connection | CODE | ELECTRICAL CHARACTERISTICS | ||||||
KVA | LOSSES | EFFICIENCY | I0 | Vcc | DV | ||||
Off Load | On Load | cosø 1 | cosø 0,7 | % | % | % | |||
0,5 | YN | ATC000K5.001 | 8,23 | 20 | 96 | 92 | 3 | 5 | 4 |
1 | YN | ATC001K0.001 | 13,2 | 47 | 96 | 92 | 3 | 4,8 | 4 |
1,5 | YN | ATC001K5.001 | 17,3 | 62 | 96 | 92,4 | 2,6 | 3,7 | 3 |
2 | YN | ATC002K0.001 | 21,6 | 77 | 96 | 92,5 | 2,6 | 3,3 | 2,8 |
2,5 | YN | ATC002K5.001 | 25,9 | 92 | 96 | 93 | 2,3 | 3 | 2,5 |
3 | YN | ATC003K0.001 | 29,7 | 98 | 97 | 94 | 2,2 | 3 | 2,3 |
4 | YN | ATC004K0.001 | 30,8 | 106 | 97 | 94 | 2 | 2,8 | 2,3 |
5 | YN | ATC005K0.001 | 35,4 | 163 | 97 | 94,6 | 2 | 2,8 | 2,3 |
7,5 | YN | ATC007K5.001 | 42,5 | 182 | 97 | 94,7 | 2 | 2,5 | 2 |
10 | YN | ATC010K0.001 | 52 | 212 | 97 | 95 | 2 | 2,3 | 1,8 |
12,5 | YN | ATC012K5.001 | 62,6 | 234 | 97 | 95 | 2 | 2 | 1,6 |
15 | YN | ATC015K0.001 | 73 | 285 | 98 | 95,6 | 1,7 | 2 | 1,5 |
20 | YN | ATC020K0.001 | 83 | 367 | 98 | 95,7 | 1,7 | 1,8 | 1,4 |
25 | YN | ATC025K0.001 | 88,4 | 411 | 98 | 96 | 1,5 | 1,8 | 1,3 |
30 | YN | ATC030K0.001 | 117,8 | 493 | 98 | 96,4 | 1,3 | 1,5 | 1,1 |
40 | YN | ATC040K0.001 | 144,3 | 556 | 98 | 96,6 | 1,3 | 1,4 | 1 |
50 | YN | ATC050K0.001 | 180,3 | 618 | 98 | 97 | 1,1 | 1,2 | 0,9 |